Series adds voltage. Parallel adds current. Here is when to use each configuration with your power station, including MPPT voltage ranges, safety limits, and real examples.

12 min read Last reviewed: February 2026 Data: 2026-02-19

When you connect two or more solar panels to a portable power station, how you wire them changes the voltage and current the station sees. Wire them wrong and you get zero charging or, worse, damage. Wire them right and you maximize solar input within your station’s limits. This guide explains the two basic configurations (series and parallel), when to use each, and how to verify safety before connecting anything.

For a broader introduction to solar panel compatibility, connectors, and charge time calculations, see our solar panels for power stations guide.

One fundamental principle to keep in mind: voltage is the only thing that can damage the input. Current just gets clipped. Exceeding a station’s maximum voltage can permanently fry the MPPT controller. Exceeding the maximum current simply reduces charging power. Both matter, but voltage mistakes are the ones you cannot undo.

Series: Voltages Add, Current Stays the Same

In a series connection, you connect the positive terminal of one panel to the negative terminal of the next, forming a chain. The result: voltages add together while current stays the same.

Single panel: Vmp 18.4V, Voc 21.5V, Imp 11.9A (220W).

Series result: Vmp 36.8V, Voc 43.0V, Imp 11.9A (440W)

Voltage doubled. Current unchanged. Total wattage doubled.

When to use series:

  1. Your panel’s Vmp is below the station’s MPPT minimum voltage. The EcoFlow DELTA Pro 3 has a primary solar port with a 30 to 150V MPPT range. A single EcoFlow 220W panel at 18.4V Vmp falls below the 30V minimum. The MPPT controller cannot lock onto the power point, and the station shows 0W input. Two panels in series produce 36.8V Vmp, which is above 30V, and the station starts charging.

  2. You want to reduce current to minimize cable losses. Higher voltage at the same wattage means lower current. Lower current means less heat in the cables and connectors, especially over long runs (20+ feet between panels and station).

The risk with series: overvoltage.

Every panel has a Voc (open circuit voltage), the maximum voltage it produces when nothing is connected. In series, Voc values add. And in cold weather (below 32 degrees F), panel Voc increases because semiconductor voltage rises as temperature drops.

The standard safety practice is to multiply the series Voc by 1.2 to account for cold conditions (this 1.2× factor is common industry practice, formalized in the National Electrical Code as NEC 690.7). If the result exceeds your station’s maximum input voltage, the overvoltage protection may trip, or the input circuitry could be permanently damaged.

Three EcoFlow 220W panels in series: Voc = 21.5V × 3 = 64.5V.

Cold-weather safety: 64.5V × 1.2 = 77.4V

This exceeds the 60V maximum of the EcoFlow DELTA 2 Max, the Anker SOLIX F3800, and most mid-range stations. Do not use this configuration with a 60V-max station.

It is safe for the EcoFlow DELTA Pro 3 primary port (150V max), the Zendure SuperBase V4600 (150V max), or the Goal Zero Yeti PRO 4000 HPP+ port (145V max).

The simple rule: Most portable panels (100W to 220W) are “12V nominal,” meaning their Voc falls between 21V and 25V. Two of these panels in series produce a cold Voc of roughly 50 to 60V, which fits most 60V-max stations. Three in series push the cold Voc to 75 to 90V, which exceeds 60V. If your station maxes out at 60V, stop at two panels in series.

Parallel: Currents Add, Voltage Stays the Same

In a parallel connection, you connect positive to positive and negative to negative using a Y-connector (also called a branch connector) or a combiner box. The result: currents add together while voltage stays the same.

Single panel: Vmp 20.7V, Voc 24.4V, Imp 4.84A (100W).

Parallel result: Vmp 20.7V, Voc 24.4V, Imp 9.68A (200W)

Current doubled. Voltage unchanged. Total wattage doubled.

When to use parallel:

  1. Your panel’s Vmp already falls within the station’s MPPT range. A single Renogy 100W panel at 20.7V Vmp is within the 11 to 60V range of most stations. Adding a second panel in parallel doubles the power without increasing voltage. No overvoltage risk.

  2. You are adding panels to a station with a low maximum voltage. The Anker SOLIX C300 accepts a maximum of 28V. A single 100W panel at 20.7V Vmp works. Two in series would produce 41.4V Vmp, well above 28V. Parallel is the only safe option for adding a second panel to this station.

  3. You have partial shade. In a series string, the output drops to the level of the weakest panel. If one panel is shaded by a tree branch, the entire string’s current drops to match the shaded panel’s reduced output (bypass diodes help but do not fully recover the loss). In parallel, each panel operates independently. The unshaded panels keep producing at full power while only the shaded one drops. If your setup involves any risk of partial shade (camping under trees, rooftop with chimney shadow), parallel is more forgiving.

The risk with parallel: overcurrent.

Total current must not exceed the station’s maximum input current per port. The EcoFlow DELTA 2 Max specifies 15A per port. Two Jackery SolarSaga 200 panels (10.0A Imp each) in parallel produce 20.0A, which exceeds 15A. The station may current-limit (reducing charging power) or overheat the input circuit. Split those panels across two ports instead, or use a station with higher current capacity.

How to Choose for Your Station

The decision follows a simple sequence. Work through it in order:

Step 1: Check single panel Vmp vs station MPPT minimum.

Is the panel’s Vmp at or above the station’s MPPT minimum voltage? If yes, parallel works. If no, you need series to reach the minimum.

Most portable panels (100W to 220W) have a Vmp between 18V and 21V. Most mid-range stations have an MPPT minimum of 11V. For these combinations, parallel is usually fine. The exception is the EcoFlow DELTA Pro 3 primary port, which requires a minimum of 30V. Low-voltage panels must be wired in series to reach that threshold.

Step 2: Check series Voc × 1.2 vs station maximum voltage.

If you need series, calculate: (panel Voc × number of panels in series) × 1.2. Is the result at or below the station’s maximum input voltage? If yes, series is safe. If no, you cannot use that many panels in series with that station.

Step 3: Check parallel Imp total vs station maximum current.

If you are using parallel, calculate: panel Imp × number of panels in parallel. Is the result at or below the station’s maximum input current per port? If yes, parallel is safe. If no, split panels across multiple ports or reduce the parallel count.

Step 4: Check total wattage vs station solar input limit.

Even if voltage and current are safe, the station’s MPPT controller will not draw more than its rated solar input. Connecting 800W of panels to a station that accepts 500W means the station charges at 500W. The excess is not used (and does not damage the station). Slight oversizing (20 to 30% above the station’s limit) is good practice because it compensates for real-world losses.

Station MPPT ranges from our database

StationMPPT RangeMax CurrentMax Solar InputNotes
Anker SOLIX C30011 to 28V8.2A100WSmall panels only. One 100W panel is the practical limit.
EcoFlow DELTA 2 Max11 to 60V15A per port500W per port (1,000W dual)Most common mid-range setup.
Anker SOLIX F380011 to 60V25A per port1,200W per port (2,400W dual)High current, but 60V ceiling limits series strings.
EcoFlow DELTA Pro 330 to 150V (primary) / 11 to 60V (secondary)15A / 20A1,600W + 1,000W (2,600W total)Primary port requires series for low-voltage panels.
Goal Zero Yeti PRO 400014 to 145V (HPP+)N/A3,000WWidest MPPT range among portable stations.

Common Configurations

Here are four practical setups using panels and stations from our database.

2 × EcoFlow 220W in series (440W, high voltage)

Vmp: 36.8V. Voc: 43.0V. Cold Voc: 43.0 × 1.2 = 51.6V. Imp: 11.9A. Safe for any station with a 60V+ maximum. Ideal for the DELTA 2 Max (11-60V, 15A) because 11.9A is well under the 15A limit and 51.6V cold Voc is under 60V. Also works on the DELTA Pro 3 primary port (30-150V), where the 36.8V Vmp clears the 30V minimum.

2 × Renogy Flex 100W in parallel (200W, moderate voltage)

Vmp: 20.7V. Voc: 24.4V. Imp: 9.68A. Safe for any station with an 11V+ minimum and 10A+ current rating. Works on the Anker C300 (28V max, 8.2A max) only if you use a single panel (9.68A exceeds the 8.2A limit). On the DELTA 2 Max (15A per port), 9.68A is fine.

2 × Jackery SolarSaga 200 in parallel (400W, moderate voltage)

Vmp: 20.0V. Voc: 24.8V. Imp: 20.0A. The 20.0A total current exceeds the DELTA 2 Max limit of 15A per port. Split across two ports (one panel per port) for 10.0A each. On the Anker F3800 (25A per port), 20.0A is safe on a single port.

4 × 100W in 2S2P (mixed series-parallel, 400W)

Two pairs of panels wired in series, then the two series strings wired in parallel. Using Renogy Flex 100W panels: Each series pair: Vmp 41.4V, Voc 48.8V, Imp 4.84A. Two pairs in parallel: Vmp 41.4V, Voc 48.8V, Imp 9.68A. Total: 400W. Cold Voc: 48.8 × 1.2 = 58.6V. Safe for 60V stations (barely). Current of 9.68A is under the 15A limit of the DELTA 2 Max.

This configuration is useful when you need more power than two panels in parallel can deliver, but cannot go full series without exceeding voltage limits.

Common Mistakes and What They Look Like

If your solar setup is not working as expected, the symptom usually points directly to the cause:

SymptomLikely CauseFix
Station shows 0W input in full sunPanel Vmp is below the station’s MPPT minimum voltageWire panels in series to raise Vmp above the minimum
Charging starts then stops (or fluctuates wildly)Series Voc is near or above the station’s max voltage; cold morning spikes push it overRemove one panel from the series string, or switch to a station with a higher voltage ceiling
Charging works but watts are much lower than expectedParallel current exceeds the station’s max input amps; the MPPT controller is current-clampingSplit panels across two ports, or rewire in series to reduce current
One shaded panel kills the whole arraySeries wiring; the shaded panel bottlenecks the stringRewire in parallel so each panel operates independently

Safety Checklist

Before connecting any solar panel configuration to your power station, verify all three limits:

1. Voltage check (overvoltage protection). Panel Voc × panels in series × 1.2 must be at or below the station’s maximum input voltage. If it exceeds the limit, reduce the number of series panels or use a station with a higher voltage ceiling. This is the most dangerous failure mode because overvoltage can permanently damage the MPPT controller.

2. Current check (overcurrent protection). Panel Imp × panels in parallel must be at or below the station’s maximum input current per port. If it exceeds the limit, split panels across multiple ports or reduce the parallel count.

3. Wattage check (input limit). Total panel wattage should be at or near the station’s solar input rating. Oversizing by 20 to 30% is acceptable (the station limits its own input). Massively oversizing wastes money on panels you cannot use.

4. Connector check. Use the correct adapter cable for your station’s input port (MC4 to XT60, MC4 to DC8020, etc.). Inspect connections for corrosion and tightness before each use. A loose MC4 connection under full sun generates heat and can melt the connector housing.

5. Never connect or disconnect panels under load. Turn off the station’s solar input (if the option exists) or cover the panels with an opaque material before plugging or unplugging connectors. Disconnecting live solar cables can produce an arc that damages connectors and poses a burn risk.

For verified panel-station pairings and charge time estimates, use our solar charge time calculator or browse our solar compatibility guides.